Alpha FXM 1100

Rugged UPS Module
Alpha FXM 1100
  • 1100W/VA UPS module designed to operate in extreme environments and provide maximum flexibility while ensuring critical loads remain protected and running during power outages and other power disturbances
  • Wide range Automatic Voltage Regulation (AVR) lengthens battery life by providing protection without transferring to backup mode during voltage surge or sag
  • Independently programmable control and report dry contacts allow monitoring and controlling of key functions
  • Temperature compensated battery charging protects batteries from overcharging or undercharging at extreme temperatures, extending the life of the battery
  • Local and remote monitoring and control via RS232 port and Ethernet SNMP interface*
  • UPS panels can be rotated, improving usability and viewing convenience
  • Description

    Alpha FXM is a line of rugged UPS power modules used worldwide in the most demanding environments where clean backup power is needed. Designed to perform in the most extreme demanding environments, Alpha FXM units ensure equipment in security, communications, traffic, industrial environments, and many other critical applications remains safe and protected from power disturbances. Thanks to its powerful programmable battery charger, the FXM is capable of providing the runtime you need. All FXM models are available in 120Vac and 230Vac.

    *Ethernet SNMP card is standard on the 120Vac model and optional on the 230Vac model

    Video


    Technical Specifications

    Electrical
    • 120Vac Model
      Battery string voltage: 48Vdc
      Nominal voltage: 120Vac
      Frequency: 60/50Hz ±5% (auto-detection)
      Input:
           Voltage range: 85 to 175Vac
           Current: 9.8A nominal
      Output:
           Waveform: Pure sinewave
           Nominal voltage: 120Vac
           Voltage regulation: +/- 10% over input voltage range
           Power at 50°C: 1100W/VA
           Frequency: Output frequency = Input frequency
      230Vac Model
      Battery string voltage: 48Vdc
      Nominal voltage: 230Vac
      Frequency: 60/50Hz ±5% (auto-detection)
      Input:
           Current: 5.1A nominal
           Voltage: 150 to 328Vac
      Output:
           Waveform: Pure sinewave
           Nominal voltage: 230Vac
           Voltage regulation: +/- 10% over input voltage range
           Power: 1100W/VA
    Mechanical
    • Dimensions:
           mm: 133H x 394W x 222D
           inches: 5.22H x 15.5W x 8.75D
      Weight: 16kg (35lbs)
    Environmental
    • Operating Temperature Range*: -40 to 74°C (-40 to 165°F)
      Audible Noise @ 25ºC: 45dBa @ 1 metre (39in)
      *Derates after 55°C
    Agency Compliance
    • Electrical safety: UL1778, CSA 22.2 No 107.3-03
      Marks: CCSAUS CE****
      EMI: Class A FCC/CISPR [EN 50091-2:1995]
      *** Compliance only applies to units with standard input and output connectors.
      Contact us for compliance information on models with optional power connectors
      ****CE applies to 230Vac version only
    Performance
    • Typical output voltage THD: <3%
      Typical efficiency: >98% (resistive load)
      Typical transfer time: <5ms