Standalone Telecom Inverter

Description
The INVERTER 2000 is a standalone DC~AC inverter system for Telecom power applications. Featuring improved efficiency, better over-load performance and compact design, the INVERTER 2000 is the solution of choice for a variety of telecom network applications. Measuring 1RU height, 19" width; it is compatible with 19" or 23" rack mounting while the built-in ATS function increases reliability by automatically switching between inverter output and other AC sources, providing extra backup for Uninterruptible power.
Technical Specifications
Electrical
-
DC Input: Nominal voltage: 48Vdc Operating range: 40 to 58Vdc Under/Over voltage warning threshold: 45/58Vdc Under/Over voltage threshold: 40/60Vdc Inrush current: .<2 x Irated Isolation DC-enclosure: 707Vdc
(Varistors and filter capacitor removed)/1minInput protection: Reverse polarity protection Psophometric noise voltage: ≤1.0mV ITU-T O.41 (16.66~6000Hz) Wide band noise: <1.0mVps of (25Hz~5KHz)
<20mVrms (25Hz~20KHz)Peak to peak noise: 150mV up to 100MHz AC Input: Voltage range: 110/115/120Vac: 89 to 138Vac
208/220/230/240Vac: 176 to 276VacOver voltage threshold: 138/276Vac Under voltage threshold: 89/176Vac Frequency range: 50/60Hz, ±2.5% Back-feed protection: Compliant with safety requirements Transfer time: Inverter to bypass: 8ms AC Output Power capacity: 2000VA/2000W Waveform: Pure sine wave Power factor: 1.0 Nominal output voltage: 110/115/120Vac or 208/220/230/240Vac Voltage regulation: Max ±2% Output frequency: 50/60Hz Frequency variation: Max ±0.5% Frequency setting: Manually, field selectable Crest factor: 3:1 THD: <3% for linear load, <5% for non-linear load Capacitive/ inductive load: –1.0 to +1.0 without exceeding permissible distortion for resistive load Efficiency: >90.5% @ full load and nominal DC input >91.5% max Current limitation: Electronic current limitation at overloads and short circuits. Isolation AC-enclosure: Basic isolation (Pri-Gnd) 2121Vdc/1min Isolation AC-DC: Reinforced isolation (Pri-Sec) 4242Vdc/1min Surge protection: EN61000-4-5.
Telcordia GR-1089 Core ANSI C62.41-IEEE,
STD 587-1980Dynamic response: <±10%, according to IEC 62040-3 class 1 Overload protection: 1.2 x Inom permanent overload capacity @ 30°C
1.5 x Inom ≥10s
2.0 x Inom ≥5s
Mechanical
-
Temperature Operation: -20 to 50°C full performance,
operating -20 to 60°CStorage -30 to 80°C Humidity: 95% relative humidity (non-condensing) Altitude: 1500m (4920ft) Heat dissipation: Forced cooling with smart control Audible noise: 55dB ETS 300 753, class 3.1
Environmental
-
Dimension: mm: 43.8H x 440W x 360D inches: 1.72H x 17.3W x 14.2D Weight: 7.1kg (15.7lbs) DC connections: 2 pole M6 studs for 2 hole compression
lugs on .625” centersAC connections (120Vac model): Input: #12x3C cord, 20A 125Vac with 5-20P (T-Blade plug) Output: 2 x NEMA 5-20R outlets, 20A 125Vac AC connections (230Vac model): Input: WS-044-7 receptacle, 16A 250Vac Output: 2 x IEC C13 outlets, 10A 250Vac