48Vdc Cordex HP 4.0kW

Modular Switched Mode Rectifier
  • Part Number: 010-623-20
  • Product Line: DC Rectifiers Modules
  • Related Categories: DC Power Solutions
48Vdc Cordex HP 4.0kW
  • High performance switches mode rectifier offers near 95% efficiency for reduced operating expenses and carbon footprint
  • Available in 75A @ 48Vdc
  • Near 95% efficiency for increased OPEX savings and reduced carbon footprint
  • Power limiting and wide range AC input
  • Hot swappable, 4RU ultra compact design
  • Backwards compatibility with Cordex 3.6kW rectifier shelves and power solutions providing cost effective upgrade path
  • Description

    Cordex High-Performance rectifiers make a proven, reliable platform even better, with significant advancements in efficiency and performance. In a compact, fan-cooled design, Alpha's HP rectifiers open the possibility for immediate Opex/Capex savings, reducing total cost of ownership and impact on the environment, and are useable under a wider range of applications.

    The Cordex HP 4.0kW is a perfect solution for various 48Vdc capacity applications from small remote sites to large power systems at CO’s, MTSO’s and Data centers. With a high operating efficiency and wide temperature operation, HP series rectifiers are also ideal for harsh outside plant enclosure installations.

    The Cordex HP 4.0kW is a backwards compatible solution with existing Cordex 3.6kW shelves and systems, providing users an easy upgrade path to greater power density and reduced OPEX.

    Local and remote setup, adjustment and control is a simple single-step process with Cordex CXC system controllers. By utilizing TCP/IP technology, complete configuration and monitoring of power equipment is possible through a network web browser.

     

    Video


    Technical Specifications

    Features
    • Indicators: AC mains OK - green LED
      Module OK - green LED
      Module fail - red LED
      Controls: CAN interface to CXC
      Adjustments:
      (via CXC controller)
      Float voltage
      Equalize voltage
      High/low voltage alarm
      High voltage shutdown
      Current limit
      Slope
      Start delay
      Protection: Current limit/short circuit
      Start delay
      Input/output fuses
      Output high voltage shutdown
      Power limiting
      Thermal foldback/shutdown
      Input transient
      AC low line foldback shutdown
    Electrical
    • 4.0kW Rectifier Module(s)
      Input voltage:
           Nominal: 208 to 277Vac
           Operating: 187 to 312Vac
           Extended: 187 to 90Vac (de-rated power)
      Input frequency: 45 to 66Hz
      Power factor: >0.99 (50 to 100% load)
      THD: <5% (@208 Vac)
      Efficiency: >94.9% peak
      Output voltage: 42 to 60Vdc
      Output power: 4000W continuous/module
      Float voltage: 48 to 58Vdc
      Output current: 74A @ 54Vdc (83.3A max. 48V)
      Load regulation: <±0.5% (static)
      Line regulation: <±0.1% (static)
      Transient response: ±3% for 40 to 90% load step
      Noise:
           Voice band: <38dBrnC
           Wide band: <30mV RMS (10kHz to 10MHz)
      <150mV pk to pk (10kHz to 100MHz)
      Psophometric noise: <2mV
      Acoustic: <60dBa @ 1m (3ft)
    Mechanical
    • Dimensions: mm: 160H x 87W x 300D
      inches: 6.3H x 3.4W x 11.8D
      Weight: 3.9kg (8.6lbs)
    Environmental
    • Temperature:
           Standard: -40 to 55°C (-40 to 149°F)
           Extended: -40 to 75°C (-40 to 167°F)
      derated power (~ 3600W @ 65°C (149°F))
           Storage: -40 to 85°C (-40 to 185°F)
      Humidity: 0 to 95% RH non-condensing
      Elevation: -500 to 4000m (-1640 to 13120ft)
      Heat dissipation: <1150 BTU per hour
    Shelves
    • Mechanical
      19"/23" shelf (5 modules)
      Dimensions:
           mm: 177H x 442W x 389D
           inches: 6.9H x 17.4W x 15.3D
      Weight: 8.5kg (19lbs)
      Mounting: Fits 19" rack flush/center mount
      Fits 23" rack center mount only
      23" shelf (6 modules)
      Dimensions:
           mm: 177H x 530W x 389D
           inches: 6.9H x 20.8W x 15.3D
      Weight: 9.5kg (21lbs)
      Mounting: Fits 23" racks only flush/center mount
      Connections
      Input: Box type terminal block
      6 to 16mm2 (10 to 6AWG)
      Output: Bus adapters with 3/8" studs on 1" centers
      Chassis ground: Compression lug
      6 to 16mm2 (10 to 6AWG)
      CAN communication: RJ 12 offset
    Standards
    • Safety: CSA C22.2 No 60950-1-03
      UL 60950-1 1st edition
      CE marked
      IEC/EN 60950-1
      EMC: ETSI 300 386
           Emissions: CFR47 (FCC) Part 15 Class B
      ICES-03 Class B
      EN55022 (CISPR 22) Class B
      C-Tick (Australia)
      EN 61000-3-2
      EN 61000-3-3
           Immunity:

      EN 61000-4-2
      EN 61000-4-3
      EN 61000-4-4
      EN 61000-4-5
      EN 61000-4-6
      EN 61000-4-11
      ANSI/IEEE C62.41 Cat B3

           NEBS: GR-1089 CORE
      GR-63 CORE