Modular DC to DC Converter Part Number: 012-548-20 |  |  | - 24 to 48VDC, 24A output
- 3RU high-density module
- Up to 3 modules per 19in or 4 modules per 23in shelves
- Scalable hot plug-in operation
- Bar graph output current indicator
The CSM11 is a compact, modular DC to DC converter system designed for communications applications. Using switched mode technology, the CSM11 provides outstanding efficiency in a compact design.
The CSM11 packs maximum power into minimum space, but doesn’t compromise on features. Paralleling diodes are included to optimize redundancy. A fully equipped CSM11 system will include up to three modules in a 19in shelf and up to four power modules in a 23in shelf — a total output capacity of 5000W per 23in shelf.
Alpha’ CSM modular DC to DC converter systems incorporate a full range of standard and optional features. |  |
| | Electrical | | Input voltage: | 20 to 30VDC | | Output voltage: | 44 to 52VDC | | Output current: | 24A max | | Power: | 1250W max | | Efficiency: | >88% (50 to 100% load) 90% typical | | Regulation: | -1%, +/-0.1% load (static) +/-0.1% line (static) <1% deviation for 50 to 100% load step (dynamic) | | Response time: | 2ms to 0.1% of output for 50 to 100% load step | | Noise: | | | Voice band: | <22dBrnC | | Wide band: | <10mV RMS (10kHz to 10MHz) <150mV pk to pk (10kHz to 100MHz) | | Psophometric: | <0.5mV | | Acoustic: | <60dBa @ 1m (3ft) | | Mechanical | | Connections: | Bullet terminals | | Dimensions: | mm: 127H x 130W x 349D inches: 5H x 5.12W x 13.75D | | Weight: | 4.6kg (10lb) | 19in shelf (3 modules) Part number: 030-650-20 | | Dimensions: | mm: 132H x 432W x 362D inches: 5.2H x 17W x 14.25D | | Weight: | 9.1kg (20lb) | 23in shelf (4 modules) Part number: 030-651-20 | | Dimensions: | mm: 132H x 533W x 362D inches: 5.2H x 21W x 14.25D | | Weight: | 9.1kg (20lb) | | Connections | | Input: | 2-hole ¼in studs on ⅝in centers (per module) | | Output: | 2 x ⅜in threaded inserts on 1in centers | | Alarms: | Terminal block 0.34 to 2.5mm2 (22 to 14AWG) | | Features | | Alarms: | Converter fail alarm major Converter fail alarm minor (jumper selectable form A/B contacts) | | Environmental | | Temperature: | 0 to 65C (32 to 149F) (standard operating) | | Optional: | -40 to 65C (-40 to 149F) (extended operating) | | Humidity: | 0 to 95% RH non-condensing | | Elevation: | -500 to 2800m (-1640 to 9186ft) |
| |
|